Kernel-4.18.0-80.el8_power_allocator

Power allocator governor tunables

Trip points

The governor works optimally with the following two passive trip points:

  1. “switch on” trip point: temperature above which the governor
    control loop starts operating. This is the first passive trip
    point of the thermal zone.

  2. “desired temperature” trip point: it should be higher than the
    “switch on” trip point. This the target temperature the governor
    is controlling for. This is the last passive trip point of the
    thermal zone.

PID Controller

The power allocator governor implements a
Proportional-Integral-Derivative controller (PID controller) with
temperature as the control input and power as the controlled output:

P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power

where
e = desired_temperature - current_temperature
err_integral is the sum of previous errors
diff_err = e - previous_error

It is similar to the one depicted below:

                                  k_d
                                   |

current_temp |
| v
| +———-+ +—+
| +—–>| diff_err |–>| X |——+
| | +———-+ +—+ |
| | | tdp actor
| | k_i | | get_requested_power()
| | | | | | |
| | | | | | | …
v | v v v v v
+—+ | +——-+ +—+ +—+ +—+ +———-+
| S |——-+—–>| sum e |—–>| X |—>| S |–>| S |–>|power |
+—+ | +——-+ +—+ +—+ +—+ |allocation|
^ | ^ +———-+
| | | | |
| | +—+ | | |
| +——->| X |——————-+ v v
| +—+ granted performance
desired_temperature ^
|
|
k_po/k_pu

Sustainable power

An estimate of the sustainable dissipatable power (in mW) should be
provided while registering the thermal zone. This estimates the
sustained power that can be dissipated at the desired control
temperature. This is the maximum sustained power for allocation at
the desired maximum temperature. The actual sustained power can vary
for a number of reasons. The closed loop controller will take care of
variations such as environmental conditions, and some factors related
to the speed-grade of the silicon. sustainable_power is therefore
simply an estimate, and may be tuned to affect the aggressiveness of
the thermal ramp. For reference, the sustainable power of a 4” phone
is typically 2000mW, while on a 10” tablet is around 4500mW (may vary
depending on screen size).

If you are using device tree, do add it as a property of the
thermal-zone. For example:

thermal-zones {
    soc_thermal {
        polling-delay = <1000>;
        polling-delay-passive = <100>;
        sustainable-power = <2500>;
        ...

Instead, if the thermal zone is registered from the platform code, pass a
thermal_zone_params that has a sustainable_power. If no
thermal_zone_params were being passed, then something like below
will suffice:

static const struct thermal_zone_params tz_params = {
    .sustainable_power = 3500,
};

and then pass tz_params as the 5th parameter to
thermal_zone_device_register()

k_po and k_pu

The implementation of the PID controller in the power allocator
thermal governor allows the configuration of two proportional term
constants: k_po and k_pu. k_po is the proportional term
constant during temperature overshoot periods (current temperature is
above “desired temperature” trip point). Conversely, k_pu is the
proportional term constant during temperature undershoot periods
(current temperature below “desired temperature” trip point).

These controls are intended as the primary mechanism for configuring
the permitted thermal “ramp” of the system. For instance, a lower
k_pu value will provide a slower ramp, at the cost of capping
available capacity at a low temperature. On the other hand, a high
value of k_pu will result in the governor granting very high power
whilst temperature is low, and may lead to temperature overshooting.

The default value for k_pu is:

2 * sustainable_power / (desired_temperature - switch_on_temp)

This means that at switch_on_temp the output of the controller’s
proportional term will be 2 * sustainable_power. The default value
for k_po is:

sustainable_power / (desired_temperature - switch_on_temp)

Focusing on the proportional and feed forward values of the PID
controller equation we have:

P_max = k_p * e + sustainable_power

The proportional term is proportional to the difference between the
desired temperature and the current one. When the current temperature
is the desired one, then the proportional component is zero and
P_max = sustainable_power. That is, the system should operate in
thermal equilibrium under constant load. sustainable_power is only
an estimate, which is the reason for closed-loop control such as this.

Expanding k_pu we get:
P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) +
sustainable_power

where
T_set is the desired temperature
T is the current temperature
T_on is the switch on temperature

When the current temperature is the switch_on temperature, the above
formula becomes:

P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) +
    sustainable_power = 2 * sustainable_power + sustainable_power =
    3 * sustainable_power

Therefore, the proportional term alone linearly decreases power from
3 * sustainable_power to sustainable_power as the temperature
rises from the switch on temperature to the desired temperature.

k_i and integral_cutoff

k_i configures the PID loop’s integral term constant. This term
allows the PID controller to compensate for long term drift and for
the quantized nature of the output control: cooling devices can’t set
the exact power that the governor requests. When the temperature
error is below integral_cutoff, errors are accumulated in the
integral term. This term is then multiplied by k_i and the result
added to the output of the controller. Typically k_i is set low (1
or 2) and integral_cutoff is 0.

k_d

k_d configures the PID loop’s derivative term constant. It’s
recommended to leave it as the default: 0.

Cooling device power API

Cooling devices controlled by this governor must supply the additional
“power” API in their cooling_device_ops. It consists on three ops:

  1. int get_requested_power(struct thermal_cooling_device *cdev,
    struct thermal_zone_device *tz, u32 *power);
    @cdev: The struct thermal_cooling_device pointer
    @tz: thermal zone in which we are currently operating
    @power: pointer in which to store the calculated power

get_requested_power() calculates the power requested by the device
in milliwatts and stores it in @power . It should return 0 on
success, -E* on failure. This is currently used by the power
allocator governor to calculate how much power to give to each cooling
device.

  1. int state2power(struct thermal_cooling_device *cdev, struct
     thermal_zone_device *tz, unsigned long state, u32 *power);
    
    @cdev: The struct thermal_cooling_device pointer
    @tz: thermal zone in which we are currently operating
    @state: A cooling device state
    @power: pointer in which to store the equivalent power

Convert cooling device state @state into power consumption in
milliwatts and store it in @power. It should return 0 on success, -E*
on failure. This is currently used by thermal core to calculate the
maximum power that an actor can consume.

  1. int power2state(struct thermal_cooling_device *cdev, u32 power,
    unsigned long *state);
    @cdev: The struct thermal_cooling_device pointer
    @power: power in milliwatts
    @state: pointer in which to store the resulting state

Calculate a cooling device state that would make the device consume at
most @power mW and store it in @state. It should return 0 on success,
-E* on failure. This is currently used by the thermal core to convert
a given power set by the power allocator governor to a state that the
cooling device can set. It is a function because this conversion may
depend on external factors that may change so this function should the
best conversion given “current circumstances”.

Cooling device weights

Weights are a mechanism to bias the allocation among cooling
devices. They express the relative power efficiency of different
cooling devices. Higher weight can be used to express higher power
efficiency. Weighting is relative such that if each cooling device
has a weight of one they are considered equal. This is particularly
useful in heterogeneous systems where two cooling devices may perform
the same kind of compute, but with different efficiency. For example,
a system with two different types of processors.

If the thermal zone is registered using
thermal_zone_device_register() (i.e., platform code), then weights
are passed as part of the thermal zone’s thermal_bind_parameters.
If the platform is registered using device tree, then they are passed
as the contribution property of each map in the cooling-maps node.

Limitations of the power allocator governor

The power allocator governor’s PID controller works best if there is a
periodic tick. If you have a driver that calls
thermal_zone_device_update() (or anything that ends up calling the
governor’s throttle() function) repetitively, the governor response
won’t be very good. Note that this is not particular to this
governor, step-wise will also misbehave if you call its throttle()
faster than the normal thermal framework tick (due to interrupts for
example) as it will overreact.